    Kyn28a-12 (GZS1-12) indoor AC metal armored central switchgear

  • Product classification:High voltage switch cabinet
  • Product specification:
  • product price:¥0.00
  • Order Hotline:13635605151

Product description

Describe

Kyn28a-12 (GZS1-12) indoor AC metal armored central switchgear (hereinafter referred to as switchgear) is an advanced medium voltage switchgear developed and provided by Xi'an Senyuan company for technology transfer. It is applicable to three-phase AC power system with rated power of 12kV and rated frequency of 50Hz. It is used to receive and distribute electric energy and control, protect and temporarily test the circuit.

Compliance with standards:

GB3906 3 ~ 35kV AC metal enclosed switchgear

Gb11022 general technical conditions for high voltage switchgear

IEC298 (1990) AC metal enclosed switchgear and control equipment with rated voltage above 1kV and below 50kV

Dl404 technical conditions for ordering indoor AC high voltage switchgear

Product model and meaning

Service environmental conditions

1. Ambient humidity: maximum temperature + 40 ℃, minimum temperature - 10 ℃

2. Ambient humidity: daily average relative humidity ≤ 95%

Monthly average relative humidity ≤ 90%

3. Altitude: below 1000m;

4. Earthquake resistance: the earthquake intensity shall not exceed 8 degrees;

5. The surrounding air does not contain corrosive or combustible gas, water vapor and other obvious pollution;

6. There is no serious pollution and frequent violent vibration, and the severity design meets class I requirements under severe conditions;

7. When it is used under normal environmental conditions beyond those specified in GB3906, it shall be negotiated between the user and the manufacturer.

Note: ① when the relative humidity is greater than 70%, turn on the electric heater.

② Places with an altitude of more than 1000m shall be treated according to JB / z102.

Technical parameter

1. See Table 1 for technical parameters of switchgear

Table1

ProjectUnitParameter
Rated voltagekV3.67.212
Rated frequencyHz50
Rated current of circuit breakerA630,1250,1600.2000,2500,3150
Rated current of switch cabinetA630,1250,1600,2000,2500,3150
Rated thermal stability current (4S)kA16,20,25,31.5,40,50,
Rated dynamic stability current (peak)kA40,50,63.80,100,125
Rated short-circuit breaking currentkA16,20,25,31,5,40,50,
Rated short-circuit making current (peak)kA40,50,63,80,100,125
Rated insulation level1min power frequency withstand voltagekV243242
Lightning impulse withstand voltagekV406075
Degree of protectionThe enclosure is IP4X, the compartment is IP2X when the fixed door of the circuit breaker is opened

2、Technical parameters of VD4 and VS1-12 vacuum circuit breaker

a、See Table 2 for technical parameters of VD4 and vs1-12j5 vacuum circuit breakers

Table2

ProjectUnitParameter
Rated voltagekV12
Rated frequencyHz50
Rated current of circuit breakerA630,1250,1600,2000,2500,3150
Rated thermal stability current (4S)kA16,20,25,31.5,40,50,
Rated dynamic stability current (peak)kA40,50,63,80,100,125
Rated short-circuit breaking currentkA16,20,25,31.5,40,50,
Rated short-circuit making current (peak)kA40,50,63,80,100,125
Rated insulation level1min power frequency withstand voltagekV42
Lightning impulse withstand voltagekV75
Rated operating sequence Opening -0.3s-closing and opening-180s-closing and opening
Rated short-circuit breaking current breaking timessecond50
Mechanical lifesecond20000

b、See Table 3 for the mechanical characteristics of VD4 and VS1 vacuum circuit breakers

Table3

NameUnitnumerical value
Contact opening distancemm11 ±1
Overtravelmm4±0.5
Interphase center distancemm210±0.5,250±0.5,275±0.5
Closing contact bounce timems≤2
Three phase opening asynchronyms≤2
The switching time is as follows:tiptopms≤50
ratedms≤50
minimumms≤60
Opening timems≤100
Average opening speedm/s0.9-1.2
Average closing speedm/s0.6-0.8
Conductive circuit resistance of each phaseUQ≤40
Contact pressureN3200±100

When the circuit breaker is used to control 3-10kV motor, if the starting current is less than 600A, metal zinc oxide arrester must be installed. The specific requirements shall be negotiated by the user and the manufacturer: when the circuit breaker is used to disconnect the capacitor bank, the rated current of the capacitor bank shall not be greater than 80% of the rated current of the circuit breaker.

3、See Table 4 for technical parameters of operating mechanism

Table4

NameUnitnumerical value
Rated operating voltageClosing coilVDC220,110,AC220,110
Opening coilVAC220,110,DC220,110
Coil powerClosing coilW245
Opening coilW245
Energy storage motor powerW50
Rated voltage of energy storage motorVDC220,110,AC220,110
Energy storage timeS≤10