- Low voltage switch cabinet
- Power distribution cabinet
- Non standard distribution box
- High voltage ring network cabinet
- High voltage switch cabinet
- High voltage sulfur hexafluoride switchgear
- High voltage arc suppression cabinet
- Constant pressure water supply equipment
- American box type substation
- European box type substation
- Lighting distribution box
- DC screen
- Integrated distribution box and console
- Product classification:High voltage switch cabinet
- Product specification:
- product price:¥0.00
- Order Hotline:13635605151
KYN61A-40.5 miniaturized armored metal enclosed switchgear
Describe
Kyn61a-40.5 miniaturized armored gold corner enclosed switchgear is designed under the auspices of Xi'an High Voltage Power Research Institute. The cabinet frame is designed according to the metal enclosed armored movable structure, and the cabinet is equipped with a new fully insulated vacuum circuit breaker or sulfur hexafluoride circuit breaker. The cabinet adopts assembly structure, which improves the appearance quality and manufacturing accuracy and shortens the production cycle. All normal operations of the switch cabinet can be carried out when the door of the high-voltage compartment is closed. This product meets the requirements of iec-60298, GB3906, dl404 and other standards, and has the "five prevention" function of complete maintenance.
The switch cabinet is used in the 40.5kV three-phase AC 50Hz power system as the power distribution room of power plants, substations and industrial and mining enterprises to receive and distribute electric energy; The circuit has the functions of control, protection and monitoring. In addition to being widely used in general power systems, it can also be used in places with frequent operation. The operating environmental conditions shall comply with the normal operating conditions specified in GB3906 3-35kv AC metal enclosed switchgear.
Product model and meaning
Service conditions
1. Ambient temperature: upper limit + 40 ℃, lower limit - 10 ℃
2. The altitude shall not exceed 1000m;
3. Relative air humidity: the daily average value shall not be greater than 95%,The monthly average value shall not be greater than 90%;
4. The seismic intensity shall not exceed 8 degrees;
5. It is not applicable to places with obvious pollution such as corrosive or combustible gas and water vapor.
Note: in case of exceeding the above normal use conditions, the user can negotiate with the manufacturer.
Technical data
Kyn61a-40.5 rated parameters of switchgear
Name | Unit | Parameter | |
Rated voltage | kV | 40.5 | |
Rated current | •A | 1250, 1600, 2000 | |
Rated short-circuit breaking current | kA | 25, 31.5 | |
Rated short-circuit making current | kA | 63, 80 | |
Dynamic stability current (peak) | kA | 63, 80 | |
4S heat stable flow (effective value) | kA | 25, 31.5 | |
Rated insulation level | Lightning impulse withstand voltage | kV | 185 |
1min power frequency withstand voltage of main circuit | 95 | ||
Overall dimension | W x D x H | m | 1.2x26x2.4 |
Degree of protection | Enclosure / Interior | m | IP3x/IP2x |
Rated parameters of zn85 a-40.5 vacuum circuit breaker
Name | Unit | Parameter | |
Rated voltage | kV | 40.5 | |
Rated current | A | 1250, 1600, 2000 | |
Rated short-circuit breaking current | kA | 25, 31.5 | |
Rated short-circuit making current | kA | 63, 80 | |
Dynamic stability current (peak) | kA | 63, 80 | |
4S heat stable flow (effective value) | kV | 25, 31.5 | |
Rated insulation level | Lightning impulse withstand voltage | kV | 185 |
1min power frequency withstand voltage of main circuit | 95 | ||
Rated frequency | Hz | 50 | |
Rated operating sequence | 0.3s-on-off 180s-on-off | ||
Mechanical life | second | 10000 | |
Closing time | Electromagnetic mechanism | s | ≤0.2 |
Spring mechanism | ≤0.15 | ||
Opening time | s | ≤0.07 |
Jn22-40.5 rated parameters of grounding switch
Name | Unit | Parameter | |
Rated voltage | kV | 40.5 | |
4S heat stable flow (effective value) | kA | 25, 31.5 | |
Dynamic stability current (peak) | kA | 63. 80 | |
Closing short-circuit current (peak) | kA | 63, 80 | |
Rated insulation level | Lightning impulse voltage | kV | 185 |
1min power frequency withstand voltage of main circuit | 95 | ||
Rated frequency | Hz | 50 |